XRUHAKXS 1x400 RMC/50 12/20kV Kabel elektroenergetyczny średniego napięcia wg PN-HD 620-10C
Information | Value |
---|---|
Supplier | NKT S.A. |
Symbol | 120325024 |
GTIN(EAN) | 8590225302697 |
Price unit | kilometer |
Catalog price | On demand |
The given prices do not constitute an offer within the meaning of the Civil Code. The purchase prices of a given item may differ from those displayed.
Description:
Kable przeznaczone do przesyłu energii elektrycznej, do zastosowania w sieciach energetycznych SN o napięciu znamionowym 12/20kV. Do układania bezpośrednio w gruncie, betonie, kanałach kablowych i bezpośrednio w powietrzu
Additional features:
Information | Value |
---|---|
ETIM class: | Power cable >= 1 kV, for permanent installation |
Conductor material: | Aluminium |
Conductor surface: | Bare |
Nominal cross section conductor: | 400 mm² |
Conductor category: | Class 2 = stranded |
Conductor resistance at 20 °C: | 0.0778 |
Shape of conductor: | Round |
Number of cores: | 1 |
Material core insulation: | Polyolefin |
Specification core insulation: | Crosslinked polyethylene (XLPE) |
Core identification according to HD 308 S2: | no |
Core identification: | None |
Laminated sheath: | yes |
Fibre optic elements: | no |
With protective conductor: | no |
Inner semi-conducting layer: | yes |
Outer semi-conducting layer: | yes |
Screen: | yes |
Lead sheath: | no |
Concentric conductor: | Copper |
Nominal cross section concentric conductor: | 50 mm² |
Armouring: | no |
Material outer sheath: | Polyolefin |
Specification material outer sheath: | Polyethylene (PE) |
Colour outer sheath: | Black |
Cable geometry: | Round |
Conductive coating: | no |
Longitudinal water blocking conductors: | no |
Longitudinal water blocking screen: | yes |
Reaction-to-fire according to EN 13501-6: Class: | Fca |
Reaction-to-fire according to EN 13501-6: Smoke production: | None |
Reaction-to-fire according to EN 13501-6: Flaming droplets/particles: | None |
Reaction-to-fire according to EN 13501-6: Acidity: | None |
Halogen free according to EN 60754-1/2: | no |
Halogen free according to EN IEC 60754-2: | no |
Flame retardant: | No |
Low smoke (according to EN 61034-2): | no |
Low smoke according to EN IEC 61034-2: | no |
Insulation integrity according to IEC 60331: | no |
Oil resistant (according to IEC 60811-404): | no |
Outer diameter approx.: | 45.2 mm |
Min. permitted bending radius, stationary application/permanent installation: | 678 mm |
Weight: | 2585 |
Max. conductor temperature: | 90 °C |
Permitted cable outer temperature during assembling/handling: | -20 - 30 °C |
Permitted cable outer temperature after assembling without vibration: | -35 - 90 °C |
Suitable as installation cable: | no |
Certified for shipboard application: | no |
Suitable as medium-voltage cable: | yes |
Suitable as high-voltage cable: | no |
Certified as airport lighting cable: | no |
Circuit integrity according to EN 50200: | No |
Circuit integrity according to EN 50200 annex E: | no |
Circuit integrity according to IEC 60331-3: | No |
Circuit integrity according to IEC 60331-21: | no |
Flame retardant according to EN 60332-1-2: | no |
Flame retardant according to EN 60332-3-21 (Cat A F/R): | no |
Flame retardant according to EN 60332-3-22 (Cat A): | no |
Flame retardant according to EN 60332-3-23 (Cat B): | no |
Flame retardant according to EN 60332-3-24 (Cat C): | no |
Flame retardant according to EN 60332-3-25 (Cat D): | no |
Halogen free according to EN 60754-1: | no |
Halogen free according to EN 60754-2: | no |
Halogen free according to EN 60754-3: | no |
Buy online
Buy / order
Wholesaler
Address
Distance
Available
Actions
Wholesalers below does not have this product in their warehouses. You can anyway contact them and order it.
Order
Wholesaler
Address
Distance
Actions
Szaflary,
ul. Zakopiańska 18
Distance:
Gniezno,
ul. Słoneczna 40a
Distance:
Limanowa,
ul. Tarnowska 9D
Distance:
Additional information:
Information | Value |
---|---|
Updated: | 2024-01-22 09:59:02 |
Files to download: |